Skip to content

Superheat & Subcooling Calculator

Calculate superheat and subcooling for R-410A, R-32, R-454B and R-22 — with the bubble-and-dew P-T chart the A2L refrigerants need, and a diagnosis that reads both numbers together.

Chemours · Arkema · NIST REFPROP manufacturer P-T data

The System

R-454BSH 15.0°F · SC 10.0°F

R-32 (68.9%) / R-1234yf (31.1%) · zeotropic, published glide ~2.0°F.

Metering device

A valve holds superheat where it wants it, so a TXV system is charged on subcooling. A piston or cap tube has nothing holding it, so superheat moves with the charge — and the target moves with the weather.

Superheat reads dew. Subcooling reads bubble.

The A2L replacing R-410A in most new US equipment from 2025. Zeotropic: Chemours states a temperature glide of ~1.1 K (~2.0 R), and the shipped table works out to about 2.3°F at both 40°F and 100°F saturation — the widget reads the real figure off the two columns at the pressure in front of you rather than quoting the nominal one. Either way, reading subcooling off the dew column, or superheat off the bubble column, is wrong by roughly two degrees before the technician has made any error of their own.

psig

Low-side gauge, read at the service port.

°F

Clamp the probe on the suction line near the service valve, under the insulation.

°F

A TXV holds superheat, so there is no formula for it — this is only here if your equipment publishes a figure to check against.

Superheat

Superheat15.0°Fmeasured superheatR-454B · dew point

Derivation

Saturation temperature at 107.0 psigR-454B PT chart · dew point40.0°F
Suction line temperatureMeasured55.0°F
Line temperature − saturation temperatureSuperheat15.0°F
Bubble-to-dew spread at this pressureGlide2.3°F

R-454B glides about 2.3°F here. Superheat is read against the dew point, which is what this figure uses — a single-column chart would read the bubble point and report roughly 2.3°F more superheat than the system actually has.

On a TXV the valve holds superheat where it wants it, so superheat is a check that the valve is working, not a charging measurement. Charge a TXV system on subcooling.

Both readings together — what the pair actually says

Neither number diagnoses anything on its own. High superheat means a starved evaporator whether the cause is a shortage of refrigerant or a restriction stopping it getting there, and the only thing that separates those two is what the high side is doing at the same moment. Enter a suction reading and a liquid reading and this reads them as a pair — the tabs above share one system, so the verdict stays live whichever one is open.

Superheat15.0°F (in band)
Subcooling10.0°F (in band)

Superheat band: 10–20°F. Subcooling band: 10.0°F ± 3°F.

Verdict

Both readings in band

Superheat and subcooling are both inside their target bands, so the charge is not what is wrong. If the system is still not performing, the fault is on the air side or in the compressor rather than in the refrigerant.

The bands above are typical published values, not the equipment's. Where the nameplate or the charging chart gives a target, that governs and this verdict does not.

On a TXV the valve holds superheat steady, so the charge shows up in subcooling. Superheat here is telling you about the valve, not the charge.

Superheat and subcooling read together — the four combinations and what each one means
SuperheatSubcoolingWhat it points at
HighLowUndercharged, or leaking — and a system that lost charge lost it somewhere.
LowHighOvercharged. Low airflow reads the same way; rule the air side out first.
HighHighLiquid line restriction — plugged drier, kinked line, or a device underfeeding.
LowLowMetering device overfeeding. Adding refrigerant here drives superheat to floodback.
In bandIn bandCharge is not the fault. Look at the air side or the compressor.

Pressure-temperature chart — bubble and dew, all four refrigerants

80 rows, -38°F to 150°F, PSIG at sea level. Use the dew column for superheat and the bubble column for subcooling — on R-454B those are two different numbers at the same gauge pressure. The rows your current readings land on are highlighted. Print this page for a field copy; the controls drop out and the chart does not.

Saturation pressure in PSIG by temperature for R-410A, R-32, R-454B and R-22, bubble point and dew point columns
Temp°FR-410AR-32R-454BR-22
BubblesubcoolDewsuperheatBubblesubcoolDewsuperheatBubblesubcoolDewsuperheatBubblesubcoolDewsuperheat
-3812.112.012.412.410.89.61.41.4
-3613.413.313.713.712.110.82.22.2
-3414.814.715.215.213.412.13.13.1
-3216.316.216.616.614.813.44.04.0
-3017.817.718.218.216.214.84.94.9
-2819.419.319.819.817.716.35.95.9
-2621.020.921.421.419.317.76.96.9
-2422.722.623.223.220.919.38.08.0
-2224.524.425.025.022.620.99.19.1
-2026.326.226.826.824.322.610.210.2
-1828.228.128.728.726.124.311.411.4
-1630.230.030.730.728.026.112.612.6
-1432.232.032.832.829.927.913.913.9
-1234.334.134.934.931.929.815.215.2
-1036.536.337.137.133.931.816.516.5
-838.738.539.439.436.133.817.917.9
-641.040.841.741.738.235.919.419.4
-443.443.244.144.140.538.120.920.9
-245.945.746.746.742.940.422.422.4
048.448.249.249.245.342.724.024.0
251.150.851.951.947.845.125.725.7
453.853.554.754.750.347.627.427.4
656.656.357.557.553.050.129.229.2
859.559.260.560.555.752.731.031.0
1062.462.263.563.558.555.432.832.8
1265.565.266.666.661.458.234.834.8
1468.668.469.869.864.461.136.836.8
1671.971.673.173.167.564.138.838.8
1875.274.976.576.570.767.140.940.9
2078.778.480.080.073.970.343.143.1
2282.281.983.683.677.373.545.345.3
2485.885.587.387.380.776.847.647.6
2689.689.291.191.184.380.350.050.0
2893.493.195.195.187.983.852.452.4
3097.497.099.199.191.787.455.055.0
32101.4101.1103.2103.295.591.157.557.5
34105.6105.2107.5107.599.594.960.260.2
36109.9109.5111.8111.8103.598.862.962.9
38114.3113.9116.3116.3107.7102.965.765.7
40118.8118.4121.0121.0112.0107.068.668.6
42123.4123.0125.7125.7116.4111.271.571.5
44128.2127.7130.5130.5120.9115.674.574.5
46133.0132.6135.5135.5125.5120.077.677.6
48138.0137.5140.6140.6130.2124.680.880.8
50143.2142.6145.8145.8135.0129.384.184.1
52148.4147.9151.2151.2140.0134.187.487.4
54153.8153.2156.7156.7145.1139.190.890.8
56159.3158.7162.4162.4150.3144.194.494.4
58164.9164.4168.1168.1155.7149.398.098.0
60170.7170.1174.0174.0161.1154.6101.6101.6
62176.7176.0180.1180.1166.7160.1105.4105.4
64182.7182.1186.3186.3172.5165.6109.3109.3
66188.9188.3192.7192.7178.3171.3113.2113.2
68195.3194.6199.2199.2184.4177.2117.3117.3
70201.8201.1205.8205.8190.5183.1121.4121.4
72208.4207.7212.6212.6196.8189.3125.7125.7
74215.2214.5219.6219.6203.2195.5130.0130.0
76222.2221.4226.7226.7209.8201.9134.5134.5
78229.3228.5234.0234.0216.5208.5139.0139.0
80236.5235.8241.5241.5223.4215.2143.6143.6
82244.0243.2249.1249.1230.4222.0148.4148.4
84251.6250.7256.9256.9237.6229.0153.2153.2
86259.3258.5264.9264.9244.9236.2158.2158.2
88267.3266.4273.0273.0252.4243.5163.2163.2
90275.4274.5281.3281.3260.0251.0168.4168.4
92283.6282.7289.8289.8267.9258.6173.7173.7
94292.1291.2298.5298.5275.8266.4179.1179.1
96300.7299.8307.4307.4284.0274.4184.6184.6
98309.5308.6316.4316.4292.3282.5190.2190.2
100318.6317.6325.7325.7300.8290.9195.9195.9
105341.9340.9349.6349.6322.8312.5210.8210.8
110366.4365.4374.9374.9345.9335.2226.4226.4
115392.3391.2401.4401.4370.2359.1242.8242.8
120419.4418.3429.3429.3395.7384.3260.0260.0
125447.9446.8458.7458.7422.4410.8278.0278.0
130477.9476.8489.5489.5450.5438.7296.9296.9
135509.4508.3521.8521.8479.9468.0316.7316.7
140542.5541.4555.8555.8510.7498.8337.4337.4
145577.3576.3591.4591.4543.0531.3359.0359.0
150613.9613.0628.8628.8576.8565.4381.7381.7

Where these numbers come from. R-22, R-32 and R-410A — both R-410A columns — agree to the printed 0.1 psig across all 80rows in three independent publications: Chemours’ Pressure-Temperature Guide for A/C, Arkema’s Forane chart, and the Daikin-branded A2L chart PM-A2LPTC-USA_04-24. R-454B is transcribed from Chemours’ own Thermodynamic Properties of Opteon™ XL41, which states NIST REFPROP v10 as its basis, and cross-checked against Chemours’ field chart. Verified 2026-08-09.

One published disagreement, named rather than averaged away. That same Daikin/Weitron chart does not match Chemours on R-454B, and only on R-454B: it runs 0.4–0.8 psig high on the dew line and up to 4.6 psig high on the bubble line, and its columns imply about 2.6°F of glide where Chemours states ~2.0°R. We ship Chemours. If Weitron turns out to be right, this chart under-reports subcooling by roughly 0.6°F at 100°F condensing.

Sea level, and your gauge knows it. A manifold reads pressure above the localatmosphere, and every P-T chart — this one and the manufacturer’s alike — is built for 14.696 psia. Higher up, the true saturation temperature is below what the chart returns, so superheat displays low and subcooling displays high. That pair is the overcharge signature, which is exactly the wrong direction to be pulled in.

The nameplate wins.Every band and target on this page is a commonly published figure, not your equipment’s. Where the unit’s own charging chart, nameplate or service literature gives a number, that one governs — and it is the only one an inspector or a warranty claim will accept. Sizing the circuit that feeds the unit is a different job: the ampacity & MCA calculator handles the Article 440 side.

How this works

Superheat and subcooling are both one subtraction, and the subtraction is not the part people get wrong. Superheat is the suction line temperature minus the saturation temperature at the suction pressure. Subcooling is the saturation temperature at the liquid line pressure minus the liquid line temperature. What matters is which saturation temperature you use, because on a blended refrigerant there are two of them at any one pressure.

A zeotropic blend boils across a range rather than at a point. The bubble point is where the last of the liquid is still liquid and the dew point is where the last of the vapor has just condensed, and the gap between them is the glide. Superheat is measured in a vapor line, so it reads the dew point. Subcooling is measured in a liquid line, so it reads the bubble point. R-454B, the refrigerant in most equipment sold in the US since 2025, glides about 2°F — so a chart printing one column is wrong by roughly two degrees no matter how carefully the reading was taken.

The two numbers only diagnose something together. High superheat says the evaporator is starved, but that is equally true of a system short on refrigerant and a system with a restriction stopping refrigerant getting there; the high side is what separates them. Low airflow across the evaporator is the confound underneath all of it, because on a fixed orifice a starved coil pushes superheat down and reads exactly like an overcharge. Whatever this page says, the equipment's own charging chart and nameplate govern.

Worked example

A fixed-orifice system on a hot, humid day: 64°F indoor wet bulb, 96°F outdoor dry bulb.

(3 × 64°F) − 80 − 96°FTarget SH = [(3 × WB) − 80 − DB] / 216
÷ 2Target SH = [(3 × WB) − 80 − DB] / 28°F target superheat
Same formula at 71°F WB / 93°F DBTarget SH = [(3 × WB) − 80 − DB] / 220°F target superheat

The target moves with the weather: 8°F on a mild day, 20°F when it's hotter and more humid outside, on the same system with no refrigerant added or removed.

Frequently Asked Questions

Do I read superheat off the bubble point or the dew point?

The dew point, always. Superheat is measured on the suction line, where the refrigerant has finished boiling and is entirely vapor, and the dew point is the temperature at which that last of the vapor would begin to condense at the pressure on your gauge. Subcooling is the mirror image: it is measured in a liquid line, so it reads the bubble point. On a single-component refrigerant like R-32 or R-22 the distinction does not exist, because the two points are the same temperature. On R-454B they are roughly 2°F apart, and swapping them costs you about 2°F on every reading before you have made any error of your own — superheat would come out about 2°F high, subcooling about 2°F low.

What is temperature glide, and which refrigerants have it?

Glide is how far the saturation temperature moves while a blend boils or condenses at constant pressure, and it exists because the components of a mixture do not change state at the same temperature. Of the four here, R-22 and R-32 are single compounds and have no glide at all. R-410A is a near-azeotrope: its bubble and dew columns differ by 0.1 to 1.0 psig, about 0.2°F, which is small but is not nothing and is carried here rather than flattened. R-454B is a genuine zeotrope of R-32 and R-1234yf; Chemours states its glide as ~1.1 K (~2.0 R), and the published data works out to about 2.3°F at both 40°F and 100°F saturation.

Why does the target superheat change with the weather?

Because on a fixed orifice — a piston or a capillary tube — nothing is regulating superheat, so it moves with how hard the system is working. The widely published approximation is [(3 × indoor wet bulb) − 80 − outdoor dry bulb] / 2: at 64°F wet bulb indoors and 96°F dry bulb outdoors the target is 8°F, and at 71°F and 93°F it is 20°F. Both of those are worked examples from published sources, re-derived here rather than copied. It is an approximation to the manufacturer's own charging chart and it should be treated as one — outside roughly the 5°F to 30°F band those charts cover, it has run past its useful range. On a TXV system none of this applies, because the valve holds superheat steady and the charge shows up in subcooling instead.

How much refrigerant do I add for a longer line set?

Most residential outdoor units ship factory charged for 15 feet of line set, and the published rate for a 3/8 inch liquid line is 0.6 ounces per foot beyond that — Goodman's TP-107 long line set guidance and Trane's installer literature both give the same figure. The trap is which length you multiply. Goodman subtracts the 15 feet the unit is already charged for; Trane's weigh-in worksheet multiplies the whole run, because it assumes the system was evacuated first and the entire charge is going in fresh. On a 50 foot run those two methods are 9 ounces apart, so read which one your manual is describing. Either way it is a starting charge, not a finished one: both manuals require a final adjustment by superheat on a fixed orifice or subcooling on a TXV.

What does high superheat with high subcooling mean?

A restriction between the condenser and the evaporator. The two readings look contradictory at first — the evaporator is starved and the condenser is backed up at the same time — but that is exactly the signature of refrigerant that is present in the system and not getting through: a plugged filter drier, a kinked or crushed liquid line, or a metering device underfeeding. It is worth knowing this one specifically because the starved evaporator on its own looks identical to an undercharge, and adding refrigerant to a restricted system raises head pressure without fixing anything. The other three combinations are: high superheat with low subcooling for undercharge, low with high for overcharge, and low with low for a metering device overfeeding.

Are these pressure-temperature numbers the same as my manufacturer's chart?

Close, and where they are not, we say so. R-22, R-32 and R-410A — including both of R-410A's columns — agree to the printed 0.1 psig at every row across three independent publications: Chemours' Pressure-Temperature Guide for A/C, Arkema's Forane chart, and the Daikin-branded A2L chart PM-A2LPTC-USA_04-24. R-454B is the exception. That Daikin chart, whose values its own footer credits to Weitron, runs 0.4 to 0.8 psig above Chemours on the dew line and up to 4.6 psig above it on the bubble line, and its columns imply about 2.6°F of glide where Chemours states ~2.0°R. We publish Chemours — the company that makes the blend, working from NIST REFPROP — and state the divergence rather than splitting the difference. All values are PSIG at sea level; above sea level the real saturation temperature is lower than any sea-level chart returns.