Skip to content

Voltage Drop Calculator

Free voltage drop calculator for electricians. Calculate voltage drop, wire size, and max distance per NEC 210.19(A) guidelines.

NEC 210.19(A), Table 8, Table 9

Circuit Details

6.47% drop✗ Exceeds NEC
Phase
1.00

1.00 for lighting/resistive loads. Motors and other inductive loads typically run 0.80–0.90 — lowering this reveals the reactance NEC Table 9 accounts for.

Conductor Material
A
ft

Voltage Drop Results

Voltage Drop %6.47%7.76 V
Voltage at Load112.24 V

✗ Exceeds NEC Recommendation (> 5%)

NEC 2023 § 210.19(A) Informational Note No. 4

Recommendation

Consider upgrading to 8 AWG/kcmil to meet the 3% branch circuit recommendation.

Exact impedance calculation — resistance (Table 8) and reactance (Table 9) at power factor 1.00, not a resistance-only approximation.

Verified against NEC 2023 · Table 8 & Table 9

How this works

Voltage drop is what happens to power as it travels down a wire. Some of it gets lost to resistance along the way, and on a long run with too small a wire, enough goes missing that motors labor, lights dim, and electronics act up before anything ever trips a breaker.

NEC 210.19(A) doesn't set a hard limit, but it recommends keeping the drop under 3% on a branch circuit and under 5% total once you add the feeder in. This calculator runs the standard formula, VD = (2 x K x I x D) / CM, using your circuit's current, one-way distance, and wire size to tell you where you land and whether you need to size up.

Heat changes the answer. A conductor's resistance rises as it gets hotter, so a run through a hot attic or rooftop conduit drops more voltage than the same wire in a cool basement. NEC Chapter 9, Table 8 has the resistance values if you need to adjust for that.

Worked example

A 16A, 120V single-phase circuit run 100 feet one-way in copper.

#12 AWG copper resistanceNEC Chapter 9, Table 81.94 Ω/kft
Voltage drop in #12 at 16A, 100 ft, 120VVD = (2 × K × I × D) / CM6.21V (5.17%)
5.17% against the 3% branch-circuit recommendationNEC 210.19(A)exceeds it
#8 AWG copper resistanceNEC Chapter 9, Table 80.79 Ω/kft
Voltage drop in #8 at the same 16A, 100 ft, 120VVD = (2 × K × I × D) / CM2.52V (2.10%)

Stepping up from #12 to #8 copper brings this 100-foot, 16A run from 5.17% voltage drop down to 2.10%, under the 3% recommendation.

Frequently Asked Questions

What is the acceptable voltage drop according to the NEC?↓

The NEC recommends a maximum voltage drop of 3% for the farthest outlet of power, heating, and lighting loads, or a maximum combined voltage drop of 5% for both the feeder and branch circuit.

How do you calculate voltage drop for single phase?↓

The formula for single-phase voltage drop is VD = (2 * K * I * D) / CM, where K is the specific resistance of the conductor, I is current in amps, D is distance in feet, and CM is circular mils of the wire.

Does temperature affect voltage drop?↓

Yes, conductor resistance increases with temperature. While standard calculations often use a fixed K-factor, high-heat environments may require adjusting the resistance values per NEC Chapter 9, Table 8.